EXQJ 1 kV 4X10/10

Description

Description

Standards

  • Product
    HD 603 S1/3L
  • National
    SS 424 14 18

Description

EXQJ is a halogen free, XLPE-insulated, HFFR-sheathed cable with circular, solid, copper conductors. The cable has a screen of annealed copper wires with opposite open helix of copper. EXQJ is designed according to HD 603. The conductors have resistance and number of wires according to IEC 60228 class 1. The cores are identified by colours according to HD 308. The cable has an extruded filler. The sheath is marked type/manufacturer/year+month/meter marking. EXQJ meets the requirements for fire classification Dcas2d2a2  according to CPR. The cable is certified by Intertek SEMKO.

Lifemark™ recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

Standards

EXQJ is manufactured and tested according to HD 603-3L in applicable parts. The cable can be loaded according to SS 424 14 24.

Certification

Approved by Intertek SEMKO.

Quality and environmental management system

Certified according to ISO 9001, ISO/TS 16949 and ISO 14001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Round, massive
Insulation
XLPE (chemical)
Outer sheath
HFFR (polyolefin)
Colour
Black
Halogen free
Yes
Conductor flexibility
Solid
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
10 mm²
Average insulation thickness
0.7 mm
Screen section
10 mm²
Average sheath thickness
1.8 mm
Nominal outer diameter
19.0 mm
Approximate weight
73.0 kg/100m
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
1.83 Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Resistance of the screen
1.83 Ohm/km

Usage characteristics

Usage characteristics

Minimum installation temperature
-10 °C
Recommended minimum installation temperature
0 °C
U.V resistance
Yes
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Length
500 m
Packaging
K9
Laying operation bending radius
152 mm
Minimum static operating bending radius
190 mm
Ambient static operating temperature, range
-40 ... 70 °C
Bending factor when installed
8 (xD)
Bending factor when laying
12 (xD)
Installation type
Indoor/Outdoor
Smoke density
IEC 61034

Resources

Resources

Selling & delivery Information

EXQJ will be delivered in lengths of 500 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Declaration of Performance

  • Declaration of Performance n� : 1000174-SEGR
  • Certification Date : 1/30/17
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close