SE-N1XE-R 1 kV 5G 16 PE-MANTEL

Description

Description

Standards

  • Product
    HD 603 S1/5O
  • National
    SS 424 14 18

SE-N1XE-R is a halogen free, XLPE-insulated, PE-sheathed cable with circular, stranded copper conductors. The cable is designed according to HD 603. The conductors have resistance and number of wires according to IEC 60228 class 2. The cores are identified by colours according to HD 308. The cable has filler. The sheath is marked type/manufacturer/year+month/metre marking. SE-N1XE-R is not flame retardant. The cable is certified by SEMKO.

 

Lifemark(TM) recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

 

Standards

SE-N1XE-R is manufactured and tested according to SS 424 14 18.The cable can be loaded in accordance with valid powercurrent regulations and SS 424 14 24.

 

Certification

Certified by SEMKO.

 

Quality and environmental management system

Certified according to ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Round, stranded
Insulation
XLPE (chemical)
Outer sheath
PE
Colour
Yellow
Halogen free
Yes
Conductor flexibility
Class 2
With Green/Yellow core
Yes
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
5
Conductor cross-section
16 mm²
Average insulation thickness
0.7 mm
Average sheath thickness
1.8 mm
Nominal outer diameter
22.0 mm
Approximate weight
100.0 kg/100m
Conductor diameter
4.8 mm
Diameter over insulation
6.2 mm
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Conductor electrical resistance
1.15 Ohm/km
Nominal impedance
2.47 Ohm
Nominal inductance
0.25 mH/km
Nominal phase capacitance
0.08 µF / km
Permissible short circuit current conductor 1s
2.3 kA
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
4 kN

Usage characteristics

Usage characteristics

Minimum installation temperature
-20 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Length
500 m
Packaging
K10
Minimum static operating bending radius
230 mm
Bending factor when installed
8 (xD)
Bending factor when laying
12 (xD)
Installation type
Outdoor - Direct burial
Rip cord
Yes

Resources

Resources

Selling & delivery Information

SE-N1XE-R will be delivered in lengths of 500 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close