AXQJ TT 24 kV 3x240/35

Description

Description

Standards

  • International
    HD 620 S2 2010 10M; IEC 60754-1; IEC 60754-2; IEC 61034-1/2
  • National
    SS 424 14 16

AXQJ TT is a longitudinally and radially waterblocked, XLPE-insulated, Cu screened and HFFR sheated 3-core cable with circular aluminium conductors.. The concentric screen and the aluminium foil has longitudinal contact. The cable is designed in applicable parts according to HD 620 S2 10M.  The conductors are longitudinally water blocked have resistance and number of wires according to IEC 60228 class 2. The sheath is marked type/manufacturer/year+month/metre marking. AXQJ TT meets the requirements for fire class Dcas2d2a2 according to CPR.


Standards

The cable can be loaded according to SS 424 14 16.


Quality and environmental management system

Certified according to ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Round, stranded
Insulation
XLPE (chemical)
Outer sheath
HFFR (Halogen Free Flame Retardant)
Colour
Black
Lead free
Yes
Conductor flexibility
Class 2
Screen
Concentric copper

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
240 mm²
Conductor diameter
18.2 mm
Average insulation thickness
5.5 mm
Screen section
35 mm²
Average sheath thickness
3.5 mm
Nominal outer diameter
76.0 mm
Approximate weight
515.0 kg/100m
Diameter over insulation
29.6 mm

Electrical characteristics

Electrical characteristics

Earth leakage current at 20 kV
3.26 A/km
Max. DC resistance of the conductor at 20°C
0.125 Ohm/km
Nominal inductance
0.3 mH/km
Nominal phase capacitance
0.3 µF / km
Operating voltage
24 kV
Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Resistance of the screen
0.6 Ohm/km

Mechanical characteristics

Mechanical characteristics

Permissible pulling forces
0.03 kN/mm²

Usage characteristics

Usage characteristics

Minimum installation temperature
0 °C
Recommended minimum installation temperature
0 °C
Maximum operating temperature
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when installed
10 (xD)
Bending factor when laying
12 (xD)
Length
500 m
Packaging
K26
Water proof
Longitudinal & radial

Resources

Resources

Selling & delivery Information

The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Declaration of Performance

  • Declaration of Performance n� : 1001170-SEGR
  • Certification Date : 6/30/23
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close