ELAQBY 10x2x1,0 MM

Description

Description

Standards

  • Test
    IEC 60332-1

Description

Design

PE-insulated, pair-twisted, screened signalling cable with halogen free, flame retardant sheath. ELAQBY 1,0 MM is used as a signalling cable in fire alarm installations. intended for fixed installation indoors and protected against mechanical damage also outdoors and in ground. Fire performance according to CPR class Dcas2d2a2. The cable emits no corrosive gases and has low smoke production during fire.

Quality and environmental management system

Certified according to ISO 9001, ISO/TS 16949 and ISO 14001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor shape
Single wired
Conductor material
Annealed copper
Insulation
PE
Screen
Aluminium copolymer
Outer sheath
HFFR (polyolefin)
Colour
Red
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Conductor diameter
1.0 mm
Number of pairs
10
Average sheath thickness
1.5 mm
Nominal outer diameter
15.7 mm
Approximate weight
31.0 kg/100m

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
24.5 Ohm/km
Max. capacity pair / core to core
55 nF/km
Ohmical resistance of the insulation
5000 MOhm.km
Maximum operating voltage
100 V

Transmission characteristics

Transmission characteristics

Attenuation, max. 800 Hz
0.7 dB/1000m

Usage characteristics

Usage characteristics

Laying operation bending radius
140 mm
Length
500 m
Packaging
K8
Ambient installation temperature, range
-10 ... 50 °C
Operating temperature, range
-40 ... 70 °C

Resources

Resources

Documentation

Selling & delivery Information

ELAQBY will be delivered in standard lengths of 500 m or cut to length according to customer request. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Declaration of Performance

  • Declaration of Performance n� : 1000043-SEGR
  • Certification Date : 11/5/18
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 0366
  • Declared performance : Dca-s2,d2,a2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close