AML 1 kV 4G50

Description

Description

Standards

  • International
    HD 603 S2/5O
  • National
    SS 424 14 18

AML is a halogen free, PP-insulated, PE-sheathed cable with stranded aluminium conductors. The cable is designed according to HD 603. The conductors have resistance and number of wires according to SS-EN 60228 class 2. The cores are identified by colours according to HD 308. The sheath is marked type/manufacturer/year+month/metre marking. AML is not flame retardant. The sheath opens with cable tear thread.

 

Lifemark(TM) recycling marking

The external surface of the outer sheath is embossed with a text which specifies all components in the polymers and prepares the cable for future recycling.

 

Standards

AML is manufactured and tested according to SS 424 14 18 i.a.p..The cable can be loaded in accordance with valid powercurrent regulations and SS 436 40 00.

 

Certification

Declaration of conformity.

 

Quality and environmental management system

Certified according to ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Insulation
PP (polypropylene)
Outer sheath
Partly recycled polyethylene
Colour
Black
Halogen free
Yes
Conductor flexibility
Class 2
Conductor shape
Sector-shaped stranded (SM)
With Green/Yellow core
Yes
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
4
Conductor cross-section
50 mm²
Average insulation thickness
1.0 mm
Average sheath thickness
1.9 mm
Nominal outer diameter
27.0 mm
Approximate weight
78.0 kg/100m
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Conductor electrical resistance
0.641 Ohm/km
Nominal impedance
1.443 Ohm
Nominal inductance at installation
0.24 mH/km
Nominal phase capacitance
0.1 µF / km
Permissible short circuit current conductor 1s
4.1 kA
Rated Voltage Uo/U (Um)
0,6/1 kV

Mechanical characteristics

Mechanical characteristics

Maximum pulling force by laying
6 kN

Usage characteristics

Usage characteristics

Minimum installation temperature
-20 °C
Maximum operating temperature
90 °C
Length
500 m
Packaging
K12
Minimum static operating bending radius
270 mm
Bending factor when installed
8 (xD)
Bending factor when laying
12 (xD)
Installation type
Outdoor - Direct burial
Minimum operating temperature
-40 °C
Rip cord
Yes

Resources

Resources

Selling & delivery Information

AML will be delivered in lengths of 500 m. The drum is marked with manufacturer, type of cable and length. The ends of the cable are sealed.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close